• buildings-slim

Andel 32 zone water detection panel

Information

Part #’s:
600007
600008

Available: 2003 TO Present

Current Model

Supported

Spares Available

Description

The Floodline 32 Zone panel is available in 2 Variants:
32 Zone
32 Zone with independent zone relays

Zones are electrically isolated from each other and individually displayed so the system can accept and report any number of simultaneous or consecutive zone alarms providing true multiple leak reporting. An alarm on 1 zone has no effect on the normal monitoring of its neighbours or the rest of the system.

The Andel Floodline 32 Zone panel has integral batteries and charging circuits which maintain protection over short power losses.

The panel has 3 relays:
1. LEAK in any zone – DPCO relay (5A @ 230VAC)
2. SYSTEM FAULT in any zone – SPCO relay (5A @ 230VAC)
3. Complete power fail – SPCO relay (5A @ 230VAC)

Optional LEAK in each individual zone – SPCO relay (1A @ 30VDC)

All relays have “clean” volt-free contacts