• buildings-slim

RLE SeaHawk LDRA6 6 Zone Panel

Information

Part #:
LDRA6

Available: 2008 –

Current Model

Supported

Spares Available

Description

The LDRA6 is a Six zone Leak Detection panel capable of monitoring up to 305 Metres of SeaHawk sensing cable per zone. The unit also has the facility to monitor switch/relay contacts allowing it to be used as a 6 channel remote alarm.

The LDRA6 requires an external 24V ac/dc power supply and is not Mains powered.

The panel has a Green power indicator and each zone has a Tricoloured led:
Power (Green)
Fault (Yellow)
Leak (Red)

For onward transmission of an alarm condition the LDRA6 has 1 Form “C” Summary Alarm Relay and 6 Form “C” alarms, one per input/zone (0.5A switching @ 120Vac)., There is also RS 232 and RS 485 communications ports.

Note: The SeaHawk LD1000 is primarily manufactured for the US market.