• buildings-slim

TraceTek TTA-SIM Alarm Panel

Information

Part #’s:
TTA-SIM-1A-120
TTA-SIM-1A-230
TTA-SIM-2-120
TTA-SIM-2-230

Available: 2004 TO Present

Current Model

Supported

Spares Available

Alternative Available

Description

The TraceTek TTA-SIM alarm panel is available with a choice of either the TT-SIM-1A (non locating) or TT-SIM-2 (locating) SIM (sensor interface module) installed.
The panel can be used as a stand alone leak detection panel or used as part of a larger TraceTek network.

The TTA-SIM has a single relay which normally closes on Leak only, although it can be factory set to be a common relay for fault and leak to special order. Note: this is a software setting and not configurable on site.

The TTA-SIM has a rugged polycarbonate enclosure for use in tough or damp environments.

The leak location of the TT-SIM-2 can be set to either Feet or Metres.